| Automatic Sprinkler
Systems Notification
Prior notification of waterflow or other tests to be made to a
sprinkler system shall be given to parties who could be affected
by an alarm.
Testing
Automatic Sprinkler Systems shall be inspected, tested and
maintained in conformance with the B.C. Fire Code by qualified
service personnel at least annually. Records are required of
Annual Inspection by qualified personnel.
Waterflow Alarm Tests
Waterflow alarm tests using the inspector's test connection
shall be performed on wet pipe sprinkler systems at intervals
not greater than twelve (12) months. Waterflow alarm tests
using the alarm test connection located at the sprinkler valve
shall be performed on sprinkler systems at intervals not greater
than one (1) month. Electrical Supervisory Signal Testing
Where an electrical supervisory signal service is provided,
transmitters and water flow actuated devices shall be tested at
intervals not greater than two (2) months. Gate-valve
supervisory switches, tank water level devices, building and
tank water temperature supervisory devices and other sprinkler
system supervisory devices shall be tested at intervals not
greater than six (6) months. Main Drain Test
A main drain test shall be conducted at intervals not
greater than twelve (12) months to ensure that the water supply
available to the sprinkler system has not deteriorated.
Trip Testing of Dry-Pipe Valves
Dry-pipe valves shall be trip tested at intervals not greater
than twelve (12) months with the control valve partially open.
Dry-pipe valves shall be trip tested at intervals not greater
than three (3) years with the control valve fully open using the
inspector's test valve.
Maintenance
Valve Inspections
Valves controlling sprinkler water supplies or alarms shall be
inspected at intervals not greater than seven (7) days to ensure
that they are in the open position. Exemption: valves which are
locked open shall be inspected at intervals not greater than one
(1) month. Valves which are electrically supervised shall be
inspected at intervals not greater than two (2) months.
Air Pressure
Air pressure on dry-pipe automatic sprinkler systems shall be
read at intervals not greater than seven (7) days, and the
system shall be maintained at the required pressure.
Winter Drainage
Auxiliary drains shall be drained before each winter.
Protection Against Freezing
Dry-pipe valve rooms or enclosures in unheated buildings
shall be inspected at intervals not greater than 24 h during
periods of freezing weather and measures shall be taken to
ensure that the temperature of the room or enclosure is
maintained above 4oC.
Records A record shall be
kept of tests and operations of each system, and this record shall
be retained for examination by the Pitt Meadows Fire Department.
Fire Department Connections
Protective caps shall be kept in place at all times on fire
department connections. Where protective caps are missing, the
fire department connections shall be examined for accumulated
refuse, back flushed when conditions warrant, and the caps
replaced. Fire department connections shall have their location
clearly identified by a visible sign, and be kept readily
accessible and clear of all obstructions, including vegetation,
for 3 feet in all directions. Hose
Stations and Cabinets
Hose stations and cabinets
shall be inspected, tested and maintained in conformance with the
B.C. Fire Code by qualified service personnel at least annually.
Records are required of Annual Inspection by qualified personnel.
Hose stations and cabinets shall be
conspicuously identified,
maintained free of obstructions,
and
inspected at intervals not
greater than one (1) month to ensure that the hose is in proper
position, and
all the equipment is in place
and in operable condition
- Hose cabinets shall be used for fire protection equipment
only.
Standpipe and hose systems having defects shall be repaired
or replaced where necessary to ensure they will operate
effectively and safely.
|