| Storage
Storage lockers are prohibited in all parking garages. No storage
is permitted in hallways or common areas. Ensure that outdoor
storage and yard areas are tidy and will not present a hazard or
hindrance to fire personnel. Commercial garbage containers must
be located either in designated fire separation rooms, or be at
least 3 meters from any combustible buildings. All containers must
have lids which are kept closed at all times. All refuse
containers located in public areas must be constructed of
non-combustible materials. Flammable
and Combustible Liquids Flammable and combustible
liquids storage shall not exceed the following amounts unless
stored within a designated and fire resistant storage room:
Class 1 liquids (gasoline) = 30
liters
Class 2 liquids (heating oil) =
150 liters
Class 3a liquids (oil) = 600
liters
Flammable and combustible liquids will
not be stored on exterior balconies No
more than 5 liters of flammable liquids may be stored in an
individual dwelling unit. Service Rooms All service
room shall be maintained in a clean and orderly fashion. No
storage may occur within service rooms (electrical, elevator,
sprinkler, mechanical, laundry). Storage of flammable materials
is strictly prohibited in service rooms. Service room doors must
be clearly identified with signage and doors must be equipped with
self-closing devices and must remain closed at all times.
Accumulation of Combustible Materials
Combustible waste materials in and around buildings shall not be
permitted to accumulate in quantities or locations that will
constitute an undue fire hazard. Combustible materials, other
than those for which the location, room or space is designed,
shall not be permitted to accumulate in any part of an elevator
shaft, ventilation shaft, means of egress, service room, service
space or common area/hallway. Horizontal concealed spaces, such
as crawl spaces and ceiling spaces, shall not be used for the
storage of combustible materials. Combustible materials shall
not be stored on a roof or adjacent to any building so as to
create a fire hazard to the building or its occupants. |